PERFORMANCE-BASED THERMO-COMPUTATIONAL METHODOLOGY FOR ESTIMATION OF THERMAL EXCLUSION ZONES IN INSTALLATIONS WITH HYDROGEN AND PETROLEUM LIQUEFIED GAS (LPG)
DOI:
https://doi.org/10.56238/IXSevenInternationalMultidisciplinaryCongress-095Keywords:
Hydrogen, Thermo Computational Modeling, Performance Based Safety, Thermal Exclusion Zones, CFD LESAbstract
Objective: This study develops the Thermo‑Computational Safety Method (TCSM) to estimate thermal exclusion zones in pressurized jets. Existing standards prescribe fixed separation distances, whereas TCSM applies dynamic thermal criteria. Methodology: We integrated Computational Fluid Dynamics – Large Eddy Simulation (CFD‑LES) with Artificial Neural Networks (ANN). A total of 1,000 scenarios were processed across 5–700 bar. Validation employed experimental data from Sandia National Laboratories (5–400 bar) and JRC HySafe correlations (400–700 bar). The model operates under a critical irradiance threshold of 12.5 kW·m⁻² and does not account for obstacles or cross‑flow wind. Originality/Relevance: TCSM reduces inference time to <0.5 ms per scenario and incorporates the physics of pressurized flames from 5 to 700 bar. The approach enables performance‑based safety engineering. Prescriptive separation distances were reduced by up to 60% for pressures below 50 bar while maintaining a safety margin ≥10%. Results: The TCSM ANN metamodel achieved a coefficient of determination (R²) of 0.988 (95% CI: 0.985–0.991) and a mean absolute error (MAE) of 0.184 m (95% CI: 0.162–0.191 m). For Renewable Natural Gas at 220 bar, TCSM predicted 15.81 m, corresponding to 164% of the 6 m prescribed by NFPA 55 (2023). This discrepancy highlights critical gaps in current normative safety frameworks. Contributions: TCSM converts thermodynamic variables into traceable regulatory criteria, reduces thermal uncertainty in pressurized jets, and enhances safety in combustible gas systems.